Description
-
Fire-Rated Access Door with Exposed Flange
Self Latching tool-key operated slam latch and ring operated slam latch
The fire rated insulated access door can be installed on fire rated walls and ceilings.
FRI Access Door Specifications
Material – 20-gauge galvanneal steel door and 16-gauge cold rolled steel frame
Hinge – Continuous piano hinge. Hinge location: Hinges must be located on the second dimension (height)
Locking mechanism – Self-latching tool-key operated slam latch and ring operated slam latch, both included
Flange – 1″ exposed flange
Frame – 2½ ” in depth, made of cold rolled steel
Rough opening – Door sizes + ¼” or + 6 mm
Insulation – 2″ thick fire rated mineral wool
Inside panel release – Mechanisms to allow panels to open from inside, standard on all doors over 12″ X 12 inches
Finish – High quality white powder coat primer
Packaging – Individually wrapped, 1 door per box
Vertical wall assemblies – Fire rated access doors, for vertical use, are subject to the following:
Certification – UL 10B (2009), NFPA 252 (2012), CAN/ULC S104 (R1985), CAN/ULC S104 (2010)
Rating Achieved – 3 hours, neutral/negative pressure
Maximum size – 48″ x 48″ (1219 mm x 1219 mm), maximum area of 2304 in², tolerance on height and width limitation is more or less 3″ (76 mm) as long as the area does not exceed 2304 in²
Temperature rise – 250°F (121°C) after 30 minutes and 450°F (232°C) after 60 minutes
Horizontal ceiling assemblies – Fire rated access doors, for horizontal use, are subject to the following:
Certification – ASTM E119 (2012), CAN/ULC S101 (2007)
Rating Achieved – 3 hours in non-combustible construction and 1 hour in combustible construction
Maximum size – 24″X36″ (610 mm X 914 mm) (hinges and latches on the side of 36″), tolerance on dimension limitations are more or less 3″ (76 mm) as long as the area does not exceed 864 in²
Temperature rise – Within allowable per ASTM E119 and CAN/ULC S101
For High security PFI-HS: Optional 14 gauge cold rolled steel frame and 16 gauge galvanneal steel door